Power Cabling

NEC-compliant conductor sizing for all system cable runs. Wire gauge selection balances code compliance, voltage drop, future expansion, and cost.

Building Layout

Panels: South-facing roof (4× Q.TRON BLK M-G2+ 430W, 4S1P string)First floor: ~10 ft ceiling heightBasement: 12 ft walls, ~30 ft wide (south to north)Main panel: North wall of basementVertical run: ~25 ft (roof penetration → basement floor)Horizontal run: ~30 ft (across basement)

Design decision: Where you place the inverter + batteries determines whether the long cable run is DC (lower voltage, more loss) or AC (higher voltage, less loss). Both options are analyzed below.

Inverter Placement Comparison

PlacementDC RunAC RunBatteryNotes
Option A: South Wall32 ft37 ft5 ftInverter + batteries on south basement wall, near roof cable entry point
Option B: North Wall62 ft5 ft5 ftInverter + batteries on north wall, adjacent to main electrical panel

DC String Cables (Panels → Inverter)

4S1P string: 131.76 V at 13.05 A (Vmp/Imp). Isc = 13.74 A. NEC 690.8(B) requires conductor ampacity >= 17.2 A (13.74 A × 1.25). Target voltage drop < 2%. Cable type: USE-2 / PV Wire (UL 4703), rated 90°C wet/dry.

Option A: South Wall — DC Run: 32 ft one-way

AWGAmpacityV DropV Drop %Power LossCable CostStatus
14 AWGmin25 A2.62 V1.99%34.2 W$19PASS
12 AWGexpansion30 A1.65 V1.26%21.6 W$29PASS
10 AWG40 A1.04 V0.79%13.5 W$51PASS
8 AWG55 A0.65 V0.49%8.5 W$67PASS
6 AWG75 A0.41 V0.31%5.4 W$96PASS

Option B: North Wall — DC Run: 62 ft one-way

AWGAmpacityV DropV Drop %Power LossCable CostStatus
14 AWG25 A5.08 V3.86%66.3 W$37FAIL
12 AWG30 A3.20 V2.43%41.8 W$56FAIL
10 AWGmin40 A2.01 V1.52%26.2 W$99PASS
8 AWGexpansion55 A1.26 V0.96%16.4 W$129PASS
6 AWG75 A0.79 V0.60%10.4 W$186PASS

DC recommendation: 10 AWG USE-2 PV Wire is the minimum code-compliant size for either placement. For future expansion headroom (second string, longer runs), step up to 8 AWG — the cost difference is ~$0.24/ft more. WindyNation 8 AWG PV Wire — 40 ft pair: $82.88

AC Output Cables (Inverter → Main Panel)

EG4 6000XP output: 240 V split-phase, 6000 W = 25.0 A. NEC continuous: 31.3 A. Target voltage drop < 3%. Cable type: THWN-2 in conduit. Requires 2 hots + 1 neutral + 1 ground (4-wire for 240V split-phase).

Option A: South Wall — AC Run: 37 ft one-way

AWGAmpacityV DropV Drop %Power LossCable CostStatus
12 AWG30 A3.66 V1.53%91.6 W$30FAIL
10 AWG40 A2.29 V0.96%57.4 W$44PASS
8 AWG55 A1.44 V0.60%36.0 W$74PASS
6 AWG75 A0.91 V0.38%22.7 W$104PASS

Option B: North Wall — AC Run: 5 ft one-way

AWGAmpacityV DropV Drop %Power LossCable CostStatus
12 AWG30 A0.49 V0.21%12.4 W$4FAIL
10 AWG40 A0.31 V0.13%7.8 W$6PASS
8 AWG55 A0.19 V0.08%4.9 W$10PASS
6 AWG75 A0.12 V0.05%3.1 W$14PASS

AC recommendation: 8 AWG THWN-2 handles either placement with ample ampacity (55 A vs 31.25 A required) and minimal voltage drop. For the short Option B run, even 10 AWG works fine. 240V split-phase needs 4 conductors (2 hot + neutral + ground). Amazon — 8 AWG THHN 4-color × 50 ft bundle: ~$226 or Home Depot Cerrowire — $48–53 per 50 ft roll

Battery Cables (Inverter → Battery Bank)

2× ECO-WORTHY Cubix 100 at 51.2 V, 100 A max combined (50 A each). NEC continuous: 125 A. Short run (~5 ft). Target voltage drop < 1% (low-voltage DC is very sensitive to loss).

Current Config: 2 Batteries (100 A, 125 A NEC)

AWGAmpacityV DropV Drop %Power LossCable CostStatus
4 AWG95 A0.308 V0.60%30.8 W$25FAIL
2 AWG130 A0.194 V0.38%19.4 W$40PASS
1/0 AWG170 A0.122 V0.24%12.2 W$55PASS
2/0 AWG195 A0.097 V0.19%9.7 W$69PASS

Expansion: 3 Batteries (150 A, 188 A NEC)

AWGAmpacityV DropV Drop %Power LossCable CostStatus
4 AWG95 A0.462 V0.90%69.3 W$25FAIL
2 AWG130 A0.291 V0.57%43.6 W$40FAIL
1/0 AWG170 A0.183 V0.36%27.4 W$55FAIL
2/0 AWG195 A0.145 V0.28%21.8 W$69PASS

Battery recommendation: 2/0 AWG battery cable. It handles the current 2-battery setup (100 A) with excellent headroom and remains code-compliant if you add a 3rd battery (150 A). WindyNation 2/0 AWG 5 ft pair with lugs: $69.38 — the cost premium over smaller gauges is negligible compared to the risk of undersizing these high-current, low-voltage runs.

Grounding

NEC 690.43 requires an equipment grounding conductor (EGC) for all exposed metal. NEC 250.122 sizes the EGC based on the overcurrent protection device (OCPD) rating.

CircuitOCPDMin EGC (Cu)Notes
DC string20 A fuse12 AWG bare or greenNEC 250.122 Table — 20 A OCPD → 12 AWG
AC output40 A breaker10 AWG bare or greenNEC 250.122 Table — 40 A OCPD → 10 AWG
Panel frames6 AWG bare copperGrounding electrode conductor per NEC 250.66
Racking6 AWG bare copperBond to building grounding system

Cable Bill of Materials

Recommended cable list assuming Option A (south wall placement) with one gauge up from minimum for DC expansion headroom.

CircuitCableColorLength$/ftCostSource
DC String (+)8 AWG USE-2 PV WireRed36 ft$1.04$37WindyNation
DC String (−)8 AWG USE-2 PV WireBlack36 ft$1.04$37WindyNation
AC Hot 1 (L1)8 AWG THWN-2Black41 ft$1.00$41Home Depot
AC Hot 2 (L2)8 AWG THWN-2Red41 ft$1.00$41Home Depot
AC Neutral8 AWG THWN-2White41 ft$1.00$41Home Depot
AC Ground10 AWG THWN-2Green41 ft$0.60$25Home Depot
DC Ground12 AWG bare CuBare36 ft$0.30$11Home Depot
Battery + / −2/0 AWG battery cable w/ lugsRed / Black10 ft$6.94$69WindyNation
GEC (panels/racking)6 AWG bare CuBare25 ft$2.00$50Home Depot
Total estimated cable cost$353

Prices sourced from WindyNation and Home Depot/Cerrowire as of March 2026. Does not include conduit, fittings, connectors, junction boxes, breakers, fuses, or disconnect switches.

Cable Types Reference

TypeUseRatingWhere
USE-2 / PV Wire (UL 4703)DC string cables90°C, 600V/1000V/2000VOutdoor, exposed, conduit, direct burial
THWN-2AC circuits in conduit90°C dry / 75°C wet, 600VInterior conduit runs
Battery cable (SGT/SGX)Inverter ↔ battery bank105°C, flexible fine-strandShort runs, high current, tight bends
Bare copperGrounding electrode conductorPanel frames, racking, ground rods

Placement Recommendation

Option A (south wall) total power loss: 44.5 W (8.5 W DC + 36.0 W AC)Option B (north wall) total power loss: 21.3 W (16.4 W DC + 4.9 W AC)

Option A saves ~-23 W in cable losses. The DC cable run is shorter (lower-voltage DC is more sensitive to distance), while the longer AC run at 240 V tolerates the distance easily. However, Option B is simpler to wire if the main panel is the natural termination point. Either works — the annual energy difference is about -42 kWh/year (assuming ~5 peak sun hours/day).

Methodology & Sources

Voltage drop formula: V_drop = 2 × L(ft) × I(A) × R(Ω/kft) / 1000 where L = one-way distance, I = operating current (Imp for DC, rated for AC).Ampacity: NEC 690.8(B) — conductor ampacity > 1.25 × Isc for PV source circuits. Based on NEC Table 310.16 at 90°C insulation rating.Resistance values: Copper at 75°C per NEC Chapter 9, Table 8.Voltage drop targets: < 2% DC (NEC 210.19 informational note),< 3% AC, < 1% battery (industry best practice for low-voltage DC).
Reference:Where to buy (priced March 2026):